-3%
Rating input voltage | 2000 VA / 1200 W |
Rating input frequency | 60/50Hz (auto sensing) |
Input phase | Single-phase |
Input socket | With Fuse |
Cold Start (0 to 100% load) | Press the ON/OFF Switch |
Power factor | 0.6 |
Rating output voltage (V) | 220 |
Waveform | Battery mode (simulated sine wave), AC mode(sine wave) |
AC Voltage Regulation | ±10% (Battery mode) |
Rear output socket | 4 x Universal – Battery backup |
Waveform | Simulated Sine Wave (Battery mode) |
Line Mode | Synchronize with the utility |
Rating frequency | 60Hz or 50 Hz ± 1 Hz |
Battery Mode | Yellow flashing |
Short circuit protection Line Mode | Fuse & Firmware protection |
Short circuit protection Battery Mode | Firmware Protection |
Overload protection Line Mode | 110%±5%; Go to fault mode Line Mode after 5 minutes, 120%±5%; Go to fault mode immediately. |
Overload protection Battery Mode | 110%±5%; Shutdown after 5 seconds, 120%±5%, Shutdown immediately |
Indicators AC mode | Green Lighting |
Indicators Battery Mode | Yellow Flashing |
Indicators Fault | Red Lighting |
Alarm Battery Mode | Sounding every 10 Seconds |
Alarm Low Battery | Sounding every Second |
Alarm Overload | Sounding every 0.5 second |
Alarm Fault | Continuously sounding |